Eaton Moeller Series Nzm Molded Case Circuit Breaker Electronic NZMS3-4-VX630/VAR

Eaton Moeller series NZM – Molded Case Circuit Breaker. NZM3 PXR20 circuit breaker, 630A, 4p, variable, screw terminal, S, 3

Product: Eaton Moeller series NZM molded case circuit breaker electronic

Description: Eaton Moeller series NZM – Molded Case Circuit Breaker. NZM3 PXR20 circuit breaker, 630A, 4p, variable, screw terminal, S, 3

đź“‹ Detailed Specifications

Parameter Value
Model Code NZMS3-4-VX630/VAR
Catalog Number 191524
Global Catalog 191524
EAN / GTIN-13 4015081920365
Length 166.0 mm
Height 275.0 mm
Width 185.0 mm
Weight 8.769 kg
Amperage Rating 630 A
Voltage Rating (AC) 690 V – 690 V
Rated Insulation Voltage (Ui) 690 V AC
Rated Operational Current (In) 630 A
Number of Poles Four-pole
Pollution Degree 3
Overvoltage Category III
Degree of Protection IP20 (basic degree of protection, in the operating controls area) | IP20
Release System Electronic release
Utilization Category A (IEC/EN 60947-2)
Overload Setting (Ir) — min 252 A
Overload Setting (Ir) — max 630 A
Instantaneous Setting (Ii) — min 1260 A
Instantaneous Setting (Ii) — max 10080 A
Short-circuit Release — min 1260 A
Short-circuit Release — max 5040 A
Short-time Withstand 0.3s 3.3 kA
Short-time Withstand 1s 3.3 kA
Ics @ 230 V 100 kA
Ics @ 400/415 V 70 kA
Ics @ 440 V 65 kA
Ics @ 525 V 18 kA
Ics @ 690 V 6 kA
Icu @ 400/415 V 70 kA
Icm @ 400/415 V 154 kA
Icm @ 440 V 143 kA
Icm @ 525 V 80 kA
Icm @ 690 V 50 kA
Uimp (main) 8000 V
Uimp (auxiliary) 6000 V
Mechanical Lifespan 15000 operations
Electrical Lifespan 3000 operations at 690 V AC-1 | 5000 operations at 415 V AC-1 | 5000 operations at 400 V AC-1
Ambient Temp — min -25 °C
Ambient Temp — max 70 °C
Standard Terminals Screw terminal
Connection Type Screw connection
Frame Type NZM3
Handle Type Rocker lever
Mounting Method Built-in device fixed built-in technique | Fixed
Application Use in unearthed supply systems at 690 V
Functions Systems, cable, selectivity and generator protection
Special Features LSI overload protection and delayed and non-delayed short-circuit protective device | R.m.s. value measurement and “thermal memory” | USB interface for configuration and test function with Power Xpert Protection Manager software | Optionally communication-capable with interface module and internal Modbus RTU module or CAM | Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit breaker (Rated short-circuit breaking capacity Icn) | Rated current = rated uninterrupted current: 630 A | Terminal capacity hint: Up to 240 mm² can be connected depending on the cable manufacturer.
Compliances RoHS conform
Certifications IEC/EN 60947 | IEC

đź“„ Specifications are sourced from official manufacturer datasheets and are provided for reference only.
For the latest official information and pricing, please contact us for an authoritative quotation.

Reviews

There are no reviews yet.

Be the first to review “Eaton Moeller Series Nzm Molded Case Circuit Breaker Electronic NZMS3-4-VX630/VAR”

Your email address will not be published. Required fields are marked *